Cartridge Cage Valves
VCZM; VCZN Three-way Cartridge Cage Valves
 |
These two position 3-way hydronic valves are intended
for use in a normal indoor environment to control the
flow of hot and/or cold water, or glycol solution to
50% concentration.
These valves can be piped for either diverting or mixing
valve applications in central heating and/or cooling
systems; or for individual fan coil, radiator or convector
applications.
Depending on the model selected they can be controlled
by either a low or line voltage SPST or SPDT controller
such as a room thermostat, aquastat or flow switch.
For trouble-free operation of the product, good installation
practice must include initial system flushing, chemical
water treatment, and the use of a 50 micron (or finer)
system side stream filter(s). Remove all filters before
flushing.
Do not use boiler additives, solder flux and wetted
materials which are petroleum based or contain mineral
oil, hydrocarbons, or ethylene glycol acetate. Compounds
which can be used, with minimum 50% water dilution,
are diethylene glycol, ethylene glycol, and propylene
glycol (antifreeze solutions).
Dimensions, Approximate: Body
Pattern: Three-way
Valve Type: Unitary
Controlled Medium: Water w/max
of 50% Glycol
Ambient Temperature Range: 32 F
to 150 F (0 C to 65 C)
Fluid Temperature Range: 34 F to
203 F (1 C to 95 C)
Timing (sec, min) when used with VC series
Actuator:
On, off models: 6 sec
Floating and modulating models: 2 min.
Maximum Close-Off Pressure: 60
psi (4 Bar)
Maximum Operating Pressure: 300
psi (20 Bar) |
Comments: characterized
cartridge for use with floating and
modulating actuators. It can be controlled by either
a low or a line
voltage spdt or spst or floating controller.
Approvals:
Canadian Standards Association: CSA Certified
Materials:
| Body |
Stem |
Packing
O-Rings |
Cartridge |
| Bronze |
Stainless Steel |
EPDM rubber |
Ryton, Noryl
engineering plastic |
|
| Product Number |
Nominal
Pipe Size |
Capacity |
Flow
Characteristics |
Pipe
Connections |
Valve Action |
Fitting
Size |
Includes |
| Cv |
Kv |
| VCZMA6100 |
1/2 in. |
3.8 Cv |
3.3 Kv |
Linear |
Sweat |
Stem up to close A port |
- |
Cartridge changing
tool |
| VCZMC6100 |
1/2 in. |
3.8 Cv |
3.2 Kv |
Linear |
Flare |
Stem up to close A port |
5/8 in. |
- |
| VCZMD6100 |
1/2 in. |
3.2 Cv |
2.7 Kv |
Linear |
Inverted Flare |
Stem up to close A port |
- |
- |
| VCZMK6100 |
3/4 in. |
6.6 Cv |
5.7 Kv |
Linear |
Female NPT |
Stem up to close A port |
- |
- |
| VCZML6100 |
3/4 in. |
5.9 Cv |
5.1 Kv |
Linear |
Sweat |
Stem up to close A port |
- |
Cartridge changing
tool |
| VCZMR6100 |
1 in. |
8.6 Cv |
7.4 Kv |
Linear |
Female NPT |
Stem up to close A port |
- |
- |
| VCZMS6100 |
1 in. |
9 Cv |
7.8 Kv |
Linear |
Sweat |
Stem up to close A port |
- |
Cartridge changing
tool |
| VCZNB6100 |
1/2 in. |
3.7 Cv |
3.2 Kv |
Linear |
Female NPT |
Stem up to close A port |
- |
- |
| VCZND6100 |
1 1/4 in. |
9 Cv |
7.8 Kv |
Linear |
Female NPT |
Stem up to close A port |
- |
- |
| VCZNE6100 |
1 1/4 in. |
9 Cv |
7.8 Kv |
Linear |
Sweat |
Stem up to close A port |
- |
Cartridge changing
tool |
| * TRADELINE models ° SUPER TRADELINE
models |
<< VOLTAR |